Back to Products

WECONPLCCompact PLC BD Module (LX5V)
BD Module: LX5V-2ADI-BD / LX5V-2ADV-BD / LX5V-2DAI-BD / LX5V-2DAV-BD
Manufacturer product pageDescription
2*Analog Current Input (4-20mA)
Specifications
| Model | Channels | Resolution | Functionality |
|---|---|
| LX 5 V-2ADI-BD | 2 | 12 | 2*Analog Current Input (4-20mA) |
| LX 5 V-2ADV-BD | 2 | 12 | 2*Analog Voltage Input(-10v-10v) |
| LX 5 V-2DAI-BD | 2 | 12 | 2*Analog Current Output (4-20mA) |
| LX 5 V-2DAV-BD | 2 | 12 | 2*Analog Voltage Output (-10v-10v) |
| Item | LX 5 V-2ADI-BD | LX 5 V-2ADV-BD |
| Current input | Voltage input |
| Analog input range | DC 4mA to 20mA (input resistor 250Ω) , absolute maximum input: -2mA, +60mA | DC-10V to 10V (input resistor 150KΩ). Note: If the input voltage exceeds ± 15V, it will be damaged. |
| Digital output | 12-bit binary |
| Resolution | 8uA (4mA to 20mA/2000) | 5mV [10V default range 1/2000] |
| Comprehensive precision | ±0.5% of full scale (4mA to 20mA: ±0.16 mA) | ± 1% of full scale |
| A/D conversion time | One scan cycle (A/D conversion after ladder diagram END instruction is executed, and BD channel map value is updated) |
| Input features | |
| Insulation | There is no insulation between the channels of the module |
| Points occupied | 0 point (2ADI is not affected by the standard maximum control points of the main PLC because it is operated through the data register) |
| Item | LX 5 V-2DAI-BD | LX 5 V-2DAV-BD |
| Current output | Voltage input |
| Analog output range | DC 4mA to 20mA (external load resistance ≤ 500 Ω) | DC -10V to 10V (external load resistance ≥ 500Ω) |
| Digital output | 12-bit binary |
| Resolution | 8uA (4mA to 20mA/2000) | 5mV [10V default range 1/2000] |
| Comprehensive precision | ±1% of full scale (4mA to 20mA: ±0.16 mA) | ± 1% of full scale |
| D/A conversion time | One scan cycle (D/A conversion after ladder diagram END instruction is executed, and BD channel output value is updated) |
| Output features | External load is 250Ω. 0 to 2000 was converted to 4mA to 20mA. |
| Insulation | There is no insulation between the channels of the module |
| Points occupied | 0 point (2DA is not affected by the standard maximum control points of the main PLC because it is operated through the data register) |