BD Module: LX5V-2ADI-BD / LX5V-2ADV-BD / LX5V-2DAI-BD / LX5V-2DAV-BD
WECONPLCCompact PLC BD Module (LX5V)

BD Module: LX5V-2ADI-BD / LX5V-2ADV-BD / LX5V-2DAI-BD / LX5V-2DAV-BD

Manufacturer product page

Description

2*Analog Current Input (4-20mA)

Specifications

ModelChannels | Resolution | Functionality
LX 5 V-2ADI-BD2 | 12 | 2*Analog Current Input (4-20mA)
LX 5 V-2ADV-BD2 | 12 | 2*Analog Voltage Input(-10v-10v)
LX 5 V-2DAI-BD2 | 12 | 2*Analog Current Output (4-20mA)
LX 5 V-2DAV-BD2 | 12 | 2*Analog Voltage Output (-10v-10v)
ItemLX 5 V-2ADI-BD | LX 5 V-2ADV-BD
Current inputVoltage input
Analog input rangeDC 4mA to 20mA (input resistor 250Ω) , absolute maximum input: -2mA, +60mA | DC-10V to 10V (input resistor 150KΩ). Note: If the input voltage exceeds ± 15V, it will be damaged.
Digital output12-bit binary
Resolution8uA (4mA to 20mA/2000) | 5mV [10V default range 1/2000]
Comprehensive precision±0.5% of full scale (4mA to 20mA: ±0.16 mA) | ± 1% of full scale
A/D conversion timeOne scan cycle (A/D conversion after ladder diagram END instruction is executed, and BD channel map value is updated)
Input features
InsulationThere is no insulation between the channels of the module
Points occupied0 point (2ADI is not affected by the standard maximum control points of the main PLC because it is operated through the data register)
ItemLX 5 V-2DAI-BD | LX 5 V-2DAV-BD
Current outputVoltage input
Analog output rangeDC 4mA to 20mA (external load resistance ≤ 500 Ω) | DC -10V to 10V (external load resistance ≥ 500Ω)
Digital output12-bit binary
Resolution8uA (4mA to 20mA/2000) | 5mV [10V default range 1/2000]
Comprehensive precision±1% of full scale (4mA to 20mA: ±0.16 mA) | ± 1% of full scale
D/A conversion timeOne scan cycle (D/A conversion after ladder diagram END instruction is executed, and BD channel output value is updated)
Output featuresExternal load is 250Ω. 0 to 2000 was converted to 4mA to 20mA.
InsulationThere is no insulation between the channels of the module
Points occupied0 point (2DA is not affected by the standard maximum control points of the main PLC because it is operated through the data register)