Back to Products

WECONPLCCompact PLC BD Module (LX5V)
BD Module: LX5V-2ADI2DAI-BD / LX5V-2ADV2DAV-BD
Manufacturer product pageDescription
2 * Thermal Resistance Input;
Specifications
| Model | Channels | Resolution | Functionality |
|---|---|
| LX 5 V-2ADI2DAI-BD | 4 | 12 bits | 2 * Analog Input/ Analog Output (4~20mA) |
| LX 5 V-2ADV2DAV-BD | 4 | 12 bits | 2 * Analog Input/ Output (-10V~10V) |
| Item | LX 5 V-2ADI2DAI-BD | LX 5 V-2ADV2DAV-BD |
| Power supply | 24VDC±10%, 50mA; 5VDC±10%, 70mA (The power supply is provided internally by host) |
| ADI section | AD V section |
| Analog input range | DC 4mA to 20mA (input resistor 250 Ω) absolute maximum input: -2mA, +30mA | DC -10V to 10V (input resistor 160KΩ). ✎Note: If the input voltage exceeds ±15V, the unit will be damaged. |
| Rated range | 4mA to 20mA: 0to 2000 (recommended) | (-10V to10V: -2000 to 2000) |
| Maximum display range | -500 to 2048 | - 2048 to 2048 |
| Resolution | 8uA (4mA to 20mA/2000) | 5 mV (10V default range 1/2000) |
| Comprehensive precision | ±0.5% of full scale (4mA to 20mA: ±0.08 mA) ±0.08 mA ) | ±0.5% of full scale |
| A/D conversion time | One scan cycle (A/D conversion after ladder diagram END instruction is executed, and BD channel mapping value is updated) |
| Input features | |
| Insulation | There is no insulation between the channels of the module |
| Points occupied | 0 point (2ADI is not affected by the standard maximum control points of the main PLC because it is operated through the data register) |
| DAI section | DA V section |
| Rated range | 0 to 2000: 4mA to 20mA | DC -10V to 10V (external load resistance ≥ 2KΩ) |
| Analog output range | DC 4mA to 20mA (external load resistance ≤ 500 Ω) | (-2000 to 2000:-10V to 10V) |
| Digital output | 12-bit binary |
| Resolution | 8uA (4mA to 20mA/2000) | 5 mV (10V default range 1/2000) |
| Comprehensive precision | ±0.5% of full scale (4mA to 20mA: ±0.08 mA) | ±0.5% of full scale |
| D/A conversion time | One scan cycle (D/A conversion after ladder diagram END instruction is executed, and BD channel output value is updated) |
| Output features | External load is 250Ω. 0 to 2000 was converted to 4mA to 20mA. |
| Points occupied | 0 point (2DAI is not affected by the standard maximum control points of the main PLC because it is operated through the data register) |