Description

2 * Thermal Resistance Input;

Specifications

ModelChannels | Resolution | Functionality
LX 5 V- 2TC2DAI-BD4 | 14/12 bits | 2 * Thermal Resistance Input ; 2 * Analog Output (4~20mA)
ProjectLX 5 V- 2TC2DAI-BD
Power supply24VDC±10%, 50mA; 5VDC±10%, 70mA (The power supply is provided internally by host)
TC Part
Input signalThermocouple: Type K or J (both types can be used per channel)
Rated rangeType K: -100℃ to 1200℃ | Type J: -100℃ to 600℃
Digital outputType K: -1000 to 12000 | Type J: -1000 to 6000
12-bit conversion, stored in 16-bit complement
Over range display32767
Measurement accuracyType K: 0.4℃ | Type J: 0.3℃
Total accuracy± (0.5% full range + 1℃) , pure water condensation point: 0℃/32℉
Conversion speed50ms*2 channels (channels that are not used are not converted)
Conversion features The readings given at the calibration reference point 0 ℃ (0), respectively. (Limited by overall accuracy)
DAI section
Rated range0 to 2000: 4mA to 20mA
Analog output rangeDC 4mA to 20mA (external load resistance ≤ 500 Ω)
Digital output12-bit binary
Resolution8uA [4mA to20mA/2000]
Comprehensive precision±0.5% of full scale (4mA to 20mA: ±0.08 mA)
D/A conversion timeOne scan cycle (D/A conversion after ladder diagram END instruction is executed, and BD channel output value is updated)
Output featuresExternal load is 250Ω. 0 to 2000 was converted to 4mA to 20mA.
Points occupied0 point (2DAI is not affected by the standard maximum control points of the main PLC because it is operated through the data register)