Description

4 * Analog Input (4~20mA)

Specifications

ModelChannels | Resolution | Functionality
LX5V-4ADI-BD4 | 12 bits | 4 * Analog Input (4~20mA)
LX5V-4ADV-BD4 | 12 bits | 4* Analog Input (-10V~10V)
ItemLX 5 V-4ADI-BD
Power supply5VDC ±10%, 70mA (The power supply is provided internally by host)
Analog input rangeDC 4mA to 20mA (input resistor 250 Ω) absolute maximum input: -2mA, +30mA
Rated range4mA to 20mA: 0to 2000 (recommended)
Maximum display range-500 to 2048
Resolution8uA (4mA to 20mA/2000)
Comprehensive precision±0.5% of full scale (4mA to 20mA: ±0.08 mA)
A/D conversion timeOne scan cycle (A/D conversion after ladder diagram END instruction is executed, and BD channel map value is updated)
Input features
InsulationThere is no insulation between the channels of the module
Points occupied0 point (4ADI is not affected by the standard maximum control points of the main PLC because it is operated through the data register)
ItemLX 5 V-4AD V -BD
Power supply5VDC ±10%, 70mA (The power supply is provided internally by host)
Analog input rangeDC -10V to 10V (input resistor 160KΩ). ✎Note: If the input voltage exceeds ±15V, the unit will be damaged.
Rated range-10V to 10V: -2000 to 2000 (Recommended)
Maximum display range-2048 to 2048
Resolution5mV (10V default range 1/2000)
Comprehensive precision±0.5% of full scale
A/D conversion timeOne scan cycle (A/D conversion after ladder diagram END instruction is executed, and BD channel mapping value is updated.)
Input features
InsulationThere is no insulation between the channels of the BD Module.
Points occupied0 point (4ADV is not affected by the standard maximum control points of the main PLC because it is operated through the data register.)