Description
2 * Thermal Resistance Input;
Specifications
| Item | LX3V-2TC2DAI-BD |
|---|---|
| Power supply | 24VDC±10% , 50mA; 5VDC±10%, 70mA (Powered by PLC host) |
| Temperature input (TC) | |
| Analog input signal | Thermocouple: K or J type, 2 channels (CH1, CH2) |
| Range of rated temperature | K: -100 ℃ - 1200 ℃ | J: -100 ℃ - 600 ℃ |
| Digital output | K: -1000 - 12000 | J: -1000 - 6000 |
| 12 bits total | |
| Accuracy | K: 0.4 ℃ | J: 0.3 ℃ |
| Overall accuracy | ±0.5% |
| Conversion rate | 50ms |
| Conversion characteristics | |
| Analog output (DAI) | |
| Rated range | 4~20mA: 0~2000 |
| Analog output | DC 4~20mA (the external load resistance is no less than 500Ω) |
| Digital output | 12 bit binary |
| Resolution | 8uA [4~20mA / 2000] |
| Precision | ±0.5% of full scale |
| AD conversion time | One PLC scanning cycle |
| Input characteristics | The external load is 250Ω and 0-2000 is converted to 4-20mA |
| Insulation | No insulation in each PLC channel |
| Occupied points | None |