Back to Products

Description
LX6V-EMB-PN Profinet Coupler Module
Specifications
| LX 6V | EMB | PN |
|---|---|
| Series | Model type EMB: Support 16 exte nsion modules EMC: Support 32 extension modules Note : Total power of modules ≤48W | Protocol: Profinet |
| Coupler Model | Extension Module Supported | Coupler Version |
| LX6V-EMB-PN LX6V-EMC-PN | LX6V-0808EXY | V1.0.0 |
| LX6V-16EX | |
| LX6V-16EY | |
| LX6V-1616EXY | |
| LX6V-32EX LX6V-32EY | |
| LX6V-4AD | |
| LX6V-4DA | |
| LX6V-4PT | |
| LX6V-4TC | |
| Item | Specifications |
| Model | LX6V-EMB-PN | LX6V-EMC-PN |
| Module supported | 16 | 32 |
| Power supply | DC 24V±10%, 100 mA ( Without expansion modules ) |
| Communication interface | RJ 45x2, 10 Mbps ( Standard Ethernet ) 、 100 Mbps ( Profinet ) |
| Communication method | Full Duplex , RT mode |
| PDO data | Up to 1440 byte |
| PDO data | Up to 1440 byte |
| Minimum communication cycle | 1ms |
| I& M data | I&M0 to I &M3 |
| Profinet version | V2.43 |
| Profinet switch | Support |
| Standard Ethernet protocol | TCP/IP, SNMP, LLDP |
| Alarm and debugging | Support update error info rmation to PLC |
| Topology | Support linear , star, tree, etc. |
| Transmission distance | The distance between two nodes should be ≤100m |
| Transmission medium | Category 5e and above |
| Priority start | Support |
| MRP | Support |
| Port Disabling | Support |
| Coupler factory reset | Support |
| Module factory reset | No support |
| Coupler firmware upgrade | Support |